Methodology version WSCC-AA 1.0 (Scoring Logic Matrix V1)

How sites are assessed

This is an operational assessment and decision-support tool. It summarises recorded evidence; it does not automatically recommend equipment replacement, and it never implies a repair, diagnosis or operational state the evidence does not establish. Every rule below is applied identically to every site and is defined in a single configuration.

What each score measures

Component weights and point allocations

ComponentWeight
Road Loops25
Counter30
Signal / Communications15
Power & Solar20
Cabinet & Site10
ComponentTestMax pointsRule
Road LoopsLoop continuity (A–L)1818 × passes ÷ expected loop count. Unused loop fields are never failures.
Road LoopsVisual condition7Good 7, OK 5, Average 3, Bad 0
CounterPowers on (known-good battery)12Yes 12, No 0 — critical
CounterFront panel8Yes 8, Partly 4, No 0
CounterLane detector cards1010 × working ÷ total
Signal / CommsHas comms3Yes 3, No 0
Signal / CommsHas details2Yes 2, No 0, N/A excluded
Signal / CommsDial / transmit data8Yes 8, No 0 — critical
Signal / CommsSignal strength2Green 2, Amber 1.5, Red 0
Power & SolarMain battery voltage8Green 8, Amber 6, Amber-low 3, Red 0
Power & SolarSolar exposure / appearance3Good 3, Vegetation 1.5, Damaged 0 (per panel)
Power & SolarSolar panel voltage3Split equally across panels; each assessed individually
Power & SolarSolar inverter3Yes 3, No 0; not applicable to 12V installations
Power & SolarInternal wiring3Yes 3, No 0
Cabinet & SiteVegetation2Good 2, Needs Attention 1, Not Accessible 0
Cabinet & SiteLocks22 × operational ÷ total
Cabinet & SiteInternal condition3All Good 3, Muddy 2, Ants 1.5, Rodent 1, Rust/water 0 (worst applies)
Cabinet & SiteWiring & terminal equipment3Yes 3, No 0

Technical thresholds

Counter type selects which thresholds apply. It is never an age penalty: a functioning Type F scores the same as a functioning BlackCat.

MeasureGreenAmberRed
Battery — legacy 6V>6.4V6.2–6.4V; 6–<6.2V (low)<6V
Battery — 12V≥12.6V12.2–<12.6V; 12–<12.2V (low)<12V
Solar panel — legacy 6V>3.2V3–3.2V<3V
Solar panel — 12V BlackCat20–23VOutside range but non-zero (requires interpretation)0V or confirmed failure
Signal — legacy counter21+11–200–10 (red signal quality)
Signal — BlackCat70.00–99.9910.00–<70.00Below 10.00 (red signal quality)

Some BlackCat counters run on 6V batteries; the voltage system is taken from the recorded counter type (e.g. “BlackCat (6v)”), then from recorded readings. Battery and solar voltages were measured disconnected and are snapshots, not measures of battery health or capacity. Signal strength measures reception, not bandwidth. Signal values converted by Excel into dates are recovered only where unambiguous (“11-20”); otherwise they are marked unclassified — a reading is never invented.

Component traffic lights

Hierarchical testing and Assessment Coverage

How Final Notes are used

Final Notes are treated as evidence through a transparent, deterministic rule set (no external AI). Evidence hierarchy: recorded technical tests → explicit notes describing the final verified condition → explicit intervention selections and repair requirements. Hedged wording (“could”, “possibly”, “may”, “likely”, “recommend”, “if”…) never creates a confirmed fault or requirement — it is flagged for review. Where notes and structured answers conflict, both are preserved and a validation warning is raised; original data is never rewritten.

RuleEffectComponent
SITE-OPERATIONALNotes describe the site as operational / nothing requiredsite
SITE-NOT-APPRAISABLESite could not be appraised (no access to equipment)site
CTR-NO-COUNTERNo counter present on sitecounter
CTR-FRONT-PANELFront panel fault describedcounter
CTR-UNRESPONSIVECounter unresponsive during testingcounter
CTR-POWER-CYCLECounter repeatedly power-cycling / resettingcounter
CTR-FAULTS-CLEAREDLogged faults self-resolved and were cleared on sitecounter
CTR-SENSOR-FAULT-REPORTEDA sensor fault is reported but not confirmed by indicators — reviewcounter
CTR-INTERNAL-SUSPECTEDPossible internal counter component faultcounter
COM-RESTORED-AFTER-RESTARTConnection restored after a restart during the visitcomms
COM-VERIFIED-WITH-KNOWN-GOOD-POWERCommunications verified working with known-good (test) powercomms
COM-INTERMITTENTIntermittent connectivity — recurring disconnections documentedcomms
COM-FAULTCommunications failure describedcomms
COM-MODEM-CORROSIONCorroded modem card contactscomms
COM-POWER-CAUSECommunications failure attributed to low battery voltage (suspected power cause)comms
COM-LOW-SIGNAL-AREALow signal area notedcomms
LOOP-NO-CONTINUITYLoss of loop continuity describedloops
LOOP-CONTINUITY-UNCERTAINEngineer could not confirm loop continuity resultsloops
LOOP-ROAD-CONDITIONRoad surface condition around loops notedloops
LOOP-TERMINATION-MONITORTermination block corrosion to be monitored (no repair required)loops
PWR-DELAMINATIONSolar panel delamination / damage describedpower
PWR-PANEL-NOT-WORKINGSolar panel(s) not working / unresponsivepower
PWR-DEAD-BATTERIESSite batteries dead / exhaustedpower
PWR-FUTURE-RISKEngineer anticipates the site may go offline (e.g. winter / low light)power
CAB-VEGETATIONVegetation clearance noted (observation, not a repair)cabinet
CAB-PESTSAnts nest / pests notedcabinet
CAB-FOLIAGE-CUTFoliage cut back during the visitcabinet

Interventions and Investment Priority

A blank repair checklist means no specific repairs were identified — not that the appraisal is incomplete. Interventions are classified as None Identified, Potential Routine, Specialist (RMA), Mixed, or Further Investigation.

ContributionMaxRule
Observed condition deterioration500.5 × (100 − Condition Score)
Specialist / intervention burden (provisional)35RMA identified 25; +5 per additional independent confirmed internal fault; suspected internal fault without RMA 12
Infrastructure concerns (provisional)15New Loops 10; Road Loop Termination Block 4; Wiring Loom / Battery Cables 5; Solar Panel(s) 3; Solar Inverter 3; Batteries 2; SIM 2; Cabinet Lock(s) 1; capped

Burden values are provisional and configurable until WSCC agrees intervention costs; they are not quotes. Only confirmed (outstanding) interventions add burden — uncertain and completed ones are listed but not counted. A score threshold never triggers a replacement recommendation.

Why equipment age is not penalised

Age does not, by itself, evidence a fault. A functioning legacy counter that passes its tests is in satisfactory condition. Counter type is used only to choose the correct technical thresholds (e.g. 6V or 12V, signal scale).

Limitations